The Avtron 7700 Resistive/Reactive Load Bank is designed for outdoor installation and offers a max capacity up to 3125 kVA.
FEATURES
- Load Capacity: Max capacity of 937.5 – 3125 KVA (see chart below).
- Standard Voltage Options: 3PH 480V or 3PH 600V.
- Load Step Resolution: 5kW/3.75 kVAr minimum.
- Controller: Remote manual toggle switch controller. Controls include: Power On/Off switch, Blower Start/ Stop push buttons, Master Load On/Off switch, and Individual Load Step switches. Visual indicators include: Power On, Blower On, and Blower/Air Failure. See Options and Spec Sheet below for other options.
- Control Power: An external 120V, 1 phase, 60 Hz supply is required for control circuit operation. An optional Control Power Transformer is available – see Options below.
- Cooling Power: External 480V, 3 phase, 60 Hz power source is required.
- Cooling: Approximately 20,000 CFM cooling per resistor stack is provided by integral TEFC or TEAO motor which is direct coupled to the cooling fan blade. Vertical airflow and discharge. The fan motor is fully protected with fuses, motor starter contractor, and overload relay.
- Resistor Load Elements: Avtron load banks use helically wound chromium alloy Helidyne elements. Elements are fully supported across their entire length by segmented ceramic insulators on stainless steel rods.
- Reactor Load Elements: Reactive elements are of non-saturating single and 3 phase iron-core construction impregnated with high dielectric varnish.
- Safety Features: A differential pressure switch provides cooling air loss protection, An over-temperature switch is provided to sense load bank exhaust temperature, Operator warning and caution statements are located on appropriate access panels.
- Load Connection: A single point connection box is provided for load connections. The connection box is designed for top entry of load cables.
- Enclosure: The skid is constructed of heavy gauge steel. The resistive and reactive load banks are constructed of aluminized steel and are designed for continuous outdoor weatherproof operation. Bolt on corner lugs or cleats are provided on the skid for overhead lifting.
- Mounting: Designed for outdoor installation on a concrete pad, structural base or trailer.
Total Capacity | Resistive / Reactive Load |
937.5 kVA at 0.8 pf | 750 kW / 562.5 kVAR |
1250 kVA at 0.8 pf | 1000 kW / 750 kVAR |
1562 kVA at 0.8 pf | 1250 kW / 937.5 kVAR |
1875 kVA at 0.8 pf | 1500 kW / 1125 kVAR |
2500 kVA at 0.8pf | 2000 kW / 1500 kVAR |
3125 kVA at 0.8pf | 2500 kW / 1875 kVAR |
DOWNLOADS
OPTIONS
- Digital Monitoring
- Control Power Transformer
- NEMA 4 Remote Control Panel Enclosure
- Automatic Load Control
- Sigma 2 Digital Controls
- Remote I/O Control
- Pilot Relay Control
- PLC Control
- Arctic Rating
- Trailer
- Other kW and Voltage Ratings
Reviews
There are no reviews yet.