— Critical Power Solutions Since 1948 —

Steadypower will be closing at noon December 24 and be closed all day December 25 for the Christmas holiday.

product Categories

Gillette SPD-2000 Standby Generator (200kW)

Please Call for Low Discount Pricing

SKU: SPD-2000 Category Tag Brand:

The Gillette SPD-2000 Standby Generator offers a Perkins diesel engine, three phase voltages, and up to 200 kW of power.

SPD-2000 Models
Model Phase, Voltage,
Power Factor
Standby Rating
kW, kVA, Amps
 SPD-2000-3-2 3 Phase, 120/208V,
0.8pf
200kW, 250kVA,
694A
 SPD-2000-3-3 3 Phase, 120/240V,
0.8pf
200kW, 250kVA,
602A
 SPD-2000-3-4 3 Phase, 277/480V,
0.8pf
200kW, 250kVA,
301A
SPD-2000-3-5 3 Phase, 127/220V,
0.8pf
200kW, 250kVA,
656A
SPD-2000-3-16 3 Phase, 346/600V,
0.8pf
200kW, 250kVA,
241A

FEATURES

  • All generator sets are USA prototype built and thoroughly tested. Production models are USA factory built and 100% load tested.
  • Solid state, frequency compensated voltage regulation is standard.
  • Electronic engine governor for precise isochronous frequency regulation.
  • Deep Sea 7420 digital controller allows programming to basic engine functions in the field. Controller has stop-manual-auto mode and engine shutdowns, signaled by full text LCD indicators. Includes power monitoring, event logging, and hour meter.
  • Heavy-duty circuit breaker is standard on all gen-sets.
  • Battery tray, cables, straps, and charger included.
  • Meets NFPA-110 Level 1 when equipped with the necessary accessories and installed per NFPA standards.
  • UL-1446 and UL-2200 certified.

ENCLOSURE OPTIONS

  • OPEN STYLE – No Enclosure: Gen-set must be placed within a weather protected area, un-inhabited by humans or animals, with proper ventilation. Silencer and flexible exhaust hose are not supplied , as installation requirements are not known. However, these two items are available as optional equipment.
  • LEVEL 2 – Aluminum Housing: Full weather protection and superior sound attenuation for specific low noise applications. Critical grade silencer is standard. Average sound level of 78 dBA at 23 ft.
Enclosure Dimensions and Weights
Enclosure Dimensions (inches)
L x W x H
Single Phase
Weight (lbs)
Three Phase
Weight (lbs)
Open Style 110 x 48 x 55 3709 3404
 Level 2 134 x 48 x 72.5 4729 4364

DIESEL FUEL TANK OPTIONS

  • Feature double-walls and emergency vents. Designed for generator sub-base installation. UL-142 Certified.
  • Available in four sizes: 353 gallons (24 hour runtime), 799 gallons (54 hour runtime), 1059 gallons (72 hour runtime) and 1488 gallons (98 hour runtime).
  • Further descriptions and tank options available here.
  • Generator can also be used with customer-supplied fuel tank.

DOWNLOADS

SPD-2000 Spec Sheet

SPD-2000 Open Drawing

SPD-2000 Enclosure Drawing

OPTIONS

  • Engine Coolant Heater
  • Starting Battery Heater Blanket
  • 10A Battery Charger Upgrade
  • 20A Battery Charger Upgrade
  • 750 CCA 12VDC Starting Battery
  • Voltage Selector Switch – modular design rotory cam for switchable voltages: 3PH 208/480 and 1PH 120/240
  • Emergency Stop Switch – mounted in a NEMA 4X small enclosure, UL Listed, Suitable for remote locations, Complies with NFPA-110 requirements
  • Emergency Stop Switch – mounted in a “Break Glass Station” NEMA 3R small enclosure, UL Listed, Suitable for remote locations, Complies with NFPA-110 requirements
  • NFPA-110 Compliance Package: Includes 16 lamp dual (8) display remote annunciators (choice of flush-mount or surface-mount) and a heavy-duty 10A 12/24 VDC battery charger
  • External Permanent Magnet Generator (PMG) for improved motor starting capabilities and un-interrupted excitation power
  • External Permanent Magnet Generator (PMG) with Digital Voltage Regulator (DVR) for improved motor starting capabilities, un-interrupted excitation power, and RMS sensing
  • Critical Grade Silencer Upgrade – for average sound level of 85 dBA at 23 ft with an Open Gen-Set (standard with Level 2 Enclosure)
  • Hospital Grade Silencer Upgrade – for average sound level of 73 dBA at 23 ft in a Level 2 Enclosure
  • R7 Foam Insulation (4-5 dBA sound reduction)
  • Paralleling Package
  • Stainless Steel Enclosure
  • Generator Enclosure Lights
  • Liquid Containment Pan – installed under frame base
  • Spring Vibration Mounts
  • Motorized Dampers
  • Isolator Mounting Pads
  • Enclosure Space Heater
  • Controller Upgrades and Alarm Interfaces
  • Asco 300 Automatic Transfer Switch (See below for a partial listing or follow this link for a full listing)
  • Five Year Extended Warranty
Model

Standby Power Rating

Phase

Voltage

Voltage Regulation

Frequency

Power Factor

Generator

Sound Level at 7m

Engine

Engine Starting System

Fuel Consumption

Dimensions LxWxH (inches)

Approximate Weight

Generator Warranty (Standby)

Engine Warranty (Standby)