The Winco DR100F4 diesel standby generator offers a 201 hp FPT N67 TM1 engine with a Stamford generator end to create a 100kW+ unit that has more engine than generator for picking up large loads or running for long periods of time. Available in several phase/voltage models. Open Skid design (POWR-PAK) or with Cabinet Enclosure (SOUND-PAK). Optional fuel tanks available. UL 2200 and CSA Listed.
Model | Phase | Voltage | kW | kVA | Amps |
DR100F4-A | 1 | 120/240V | 100 | 100 | 417 |
DR100F4-D | 3 | 120/208V | 105 | 131 | 364 |
DR100F4-J | 3 | 120/240V | 105 | 131 | 315 |
DR100F4-L | 3 | 277/480V | 115 | 143 | 170 |
FEATURES
Engine Features
- FPT 201 hp diesel engine.
- EPA Certified Tier 3.
- Efficient low fuel consumption design.
- Precision Italian manufacturing.
- Complete service network (including most CASE and New Holland Dealers).
- Circulating block heater – 120V, 1000W, with thermostat.
Generator Features
- Stamford industrial grade generator.
- Rated for continuous standby use.
- Class H insulation.
- Automatic voltage regulator provides +/-1.5% regulation.
- Available in all common voltages.
Control Features
- Digital genset DSE 7310 controller.
- Engine/genset display and protection.
- Glow plugs and starter solenoid controls.
- Emergency stop.
- USB connectable communications.
- Expanded communications options.
- Audible alarm.
- Engine exerciser.
- Event log.
- Configurable inputs.
- Configurable outputs.
- UL/CSA Listed.
- See the Spec Sheet below for a full listing of features.
Other Features
- Open Skid Design (Sound Attenuated Cabinet available)
- Welded and powder coated steel base.
- Rubber mounted engine and generator.
- Electrician friendly single cover connection points.
- 2A batter charger.
- Load bank tested.
- Single step 100% load tested.
- Operation Manuals.
- Designed for long life.
SOUND-PAK Cabinet Option
- Constructed with Galvannealed steel
- Lockable doors keyed alike
- Stainless steel hinges and door stops
- Critical muffler
- Maintenance doors and panels
- Powder coated prior to assembly
- Sound absorbing foam lined
- Cooling air deflectors
DOWNLOADS
OPTIONS
Fuel Tanks
- 230 gallon base mounted steel double wall fuel tank – UL142 Listed
- 415 gallon base mounted steel double wall fuel tank – UL142 Listed
Other Options
- NFPA 110 Level 1 Compliant Upgrade
- 10 Amp Battery Charger with with Fail Contact
- Generator Strip Heater
- Battery Heater
- Group 24 650 CCA Battery
- Permanent Magnet Generator (PMG) MX321 Upgrade (0.5% regulation)
- Remote Emergency Stop
- DSE7310 Controller Options: Remote Annunciator, Remote Display, WebNet Gateway, GSM Antenna, GPS Antenna