The Asco 300 Power Meter 5210 monitors provides enhanced energy and power information.
FEATURES
- Enhanced monitoring features include power metering, energy consumption, and power demand.
- For use with Asco 300 transfer switches with Group G Controller – sized by transfer switch amp size.
- Setup provided from the front of the module includes CT rating (xxxxx:5), PT rating (xxxxxxx:120) (if applicable; 24000V maximum), System type (single or three phase; 3 or 4 wire), and Communication parameters.
- Continuous duty, long life, 4 line x 20 character LCD backlit display provides monitoring via menu scroll buttons.
- Capable of interfacing with an optional Quad Ethernet Module 72EE to permit information to be sent to a central location for display, analysis, and logging (when used with an Asco 300 transfer switch only).
LCD Display Monitoring
- Current per phase RMS and neutral (if applicable).
- Current Unbalance %.
- Voltage, phase to phase and phase to neutral.
- Voltage Unbalance %.
- Real power (kW): per phase and 3 phase total.
- Apparent power (kVA): per phase and 3 phase total.
- Reactive power (kVAR): per phase and 3 phase total.
- Power factor: per phase and 3 phase total.
- Frequency.
- Accumalted Energy, (MWH,MVAH, and MVARH).
- Total harmonic distortion.
Optional Monitoring with 72EE Module
- Current per phase RMS and neutral (if applicable).
- Current Unbalance %.
- Voltage, phase to phase and phase to neutral.
- Voltage Unbalance %.
- Real power (kW): per phase and 3 phase total.
- Apparent power (kVA): per phase and 3 phase total.
- Reactive power (kVAR): per phase and 3 phase total.
- Power factor: per phase and 3 phase total.
- Frequency.
- Accumalted Energy, (MWH,MVAH, and MVARH).
- Total harmonic distortion.
- Accumulated real energy KWH.
- Accumulated reactive energy KVAH.
- Accumulated apparent energy KVARH.
Please Note: Power Meter 5210 cannot be used with Asco 300 Load Current Metering Cards (Accessory 23GA/23GB).
Reviews
There are no reviews yet.