— Critical Power Solutions Since 1948 —

product Categories

Thomson TS970 Automatic Transfer Switch (3Ph, 4-Pole, 150A)

Price range: $3,175.00 through $3,380.00

SKU: TS974A0150A1C-x-6-x-JJAA Category Tag Brand:
Availability: Please Call for Current Lead Time
Shipping: Free Shipping in the Continental U.S.

This Thomson TS970 Automatic Transfer Switch is ideal for transferring light commercial & industrial three phase switched neutral loads up to 150A.

TRANSFER SWITCH FEATURES

  • Employs a power contactor switching unit and the TSC 7320 controller to automatically start a generator and transfer system load in the event of a utility supply failure.
  • Automatically re-transfers back to the utility supply following restoration of the utility power source to within normal operating limits.
  • All load transfer sequences are “Open Transition” (i.e. “break-before-make”) with in-phase transfer detection, or with adjustable neutral position delay to ensure adequate voltage decay for preventing out of phase transfers.
  • 150A, 3-Phase, 60Hz, 4-Wire, 4-Pole, Switched Neutral.
  • 3 cycle withstand current tested in accordance with UL 1008 & CSA 178.
  • Can withstand 6 times overload for 10 cycles.
  • Rated for 100% system load.
  • Power contactor switching units offering 100% Continuous Current Ratings for use with all load types, High Short Circuit Withstand Ratings, Three Position Power Contactor with programmable neutral delay, Single Coil Power Contactor Design for reliable operation, Jumper configurable control voltage with no need to change solenoids, and Electrically and Mechanically Interlocked mechanism preventing simultaneous closure between Utility and Generator sources.
  • Superior serviceability with enclosed Power Contacts for safe operation and maintenance, front-accessible control wires and cable connections, and a plug-in TSC 7320 Transfer Switch Controller.
  • Seismic Certified for installation and operation per the following requirements: Standards: IBC 2018, ASCE7 – 16, ICCES – AC156 – 2015; Maximum Design Loads, SDS(g)=2.5, Ip=1.5, Fp/Wp – 1.88.
  • Certified to CSA 178 & UL 1008 Standards.
  • NEMA 1 indoor standard. Optional NEMA 3R outdoor enclosures also available.
  • Note: Molded case circuit breakers or fuses with over-current protection are required upstream of the transfer switch.
  • Not Service Entrance Rated.

TSC7320 CONTROLLER FEATURES

  • Isolation plug permits disconnecting control circuits from all power sources.
  • 2.3” back-lit LCD text display for monitoring Utility/Generator voltage, system frequency, operation status, and alarms.
  • All parameters and configurations are entered without opening the front door.
  • Five key menu navigation.
  • Front-panel editing with PIN protection.
  • Customizable status screens.
  • Load on Utility & Load on Generator indication.
  • Utility & Generator Source available indication.
  • 3 Phase Voltage sensing on Utility & Generator Sources.
  • Generator AC frequency sensing.
  • Utility under voltage control setpoint 50 – 95% (adjustable).
  • Generator under voltage control setpoint 50 – 95% (adjustable).
  • Generator under frequency control setpoint 70 – 90% (adjustable).
  • Engine warm-up timer 0-60 min. (adjustable).
  • Utility return timer 0-60 min. (adjustable).
  • Engine start (mains transient) delay timer 0-30 sec. (adjustable).
  • Engine cooldown timer 0-60 min. (adjustable).
  • Neutral position delay timer 0-120 sec. (adjustable).
  • Load Disconnect Contact (LDC) for pre/post transfer control to signal external building systems such as elevators during transfer operations.
  • Up to 16 different date and time schedules for On-load or Off-load Generator exercising.
  • Real-time clock provides accurate event logging.
  • Data logging.
  • Five Programmable Outputs.
  • Five pre-programmed outputs for ATS functionality: Load on Utility, Load on Gen, Load Disconnect Contact (LDC), Fail to Transfer (FTT), and ATS Not in Auto.
  • Local and remote utility power fail simulation test.
  • Engine start contact (8A, 120/250VAC resistive max.).
  • Automatic force transfer to alternate supply should load voltage become de-energized.
  • 24VDC control power.
  • Remote Load Test/Peak Shave Input.
  • Under/Over Frequency Protection- Utility and Generator Sources.
  • 3 Phase Over Voltage Protection – Utility and Generator Sources.
  • Phase Sequence and Phase Rotation Protection between Utility and Generator Sources.
  • Voltage Phase Loss/Unbalance Protection.
  • Five user-programmable Inputs (14 inputs total).
  • RS485 Modbus Remote Communication Port (Modbus Serial RTU).
  • Serviceable Plug-in Connectors.

PRODUCT DOWNLOADS

TS970 Brochure

TS970 Manual

TSC7320 Controller Manual

TS970 4P 150-250A Drawing

Thomson ATS Comparison Guide

OPTIONS

Auxiliaries

  • KOTS-DSE – Key Operated Test Switch- Auto/Off/Engine Start/Test- includes DSE2130 module.
  • R02157 – Programmable Relay Output Expansion Module – Includes eight 2A Resistive 30VDC rate relays – four NO and four Form C Contacts.
  • PPR-10-DSE – Programmable Power Relay includes 10A Form C Contact wired to terminal block (Up to Qty 3).

Communication

  • RA7320 (DSE2548) – Remote Annunciator with eight configurable LEDs. Works up to 0.6 miles from the ATS TSC7320 controller. Up to ten modules can be daisy chained.
  • RD7320 (DSE2520) – Remote Display – up to three display modules can be connected to the TSC7320.
  • EMB-TCP/IP-DSE-MOXA – Ethernet ModbusTM Remote Communication Port (ModbusTM TCP).

Enclosure

  • LCK – Enclosure Lockable Door (Single point T-Handle lock).
  • TS-H1 – Enclosure Strip Heater c/w Thermostat (120VAC external power source required).
  • TS-H2 – Enclosure Strip Heater c/w Thermostat (internally powered from ATS load).

Function

  • LSC – Load Shed – 5-Stage (requires CTK option).
  • 480VDELTA-DEEPSEA – Control Transformers for 100-400A, 480V Delta Systems without Neutral Connection (3 Phase, 3 Wire).

Metering

  • LPM-DSE – Transfer Switch Generator Power Metering CT Kit (Amp, Volt, Freq, kW, kVA, PF) **Requires CT Kit.
  • CTKxxxxDSE – Current Transformer Kit. Specify CT size: 0100, 0150, 0250, 0400, 0600, 0800, 1000, 1200. Require LPM option.

Power

  • SPD – Surge Protection Device.
Phase

Poles

VAC (4-Wire System)

,

Frequency

Amps

Withstand Rating

Lugs per Phase

Cabinet Type

Service Entrance Rated

Full Dimensions HxWxD (inches)

Shipping Weight

Limited Warranty

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.

ACCESSORIES